Description:
They are made of epoxy resin With Brass fitting.
The insulators are for indoor.
Use in environment with max temperature of 85°C.
These insulators used as insulating supports for electrical equipment, bus bars, fuses & etc.
Reference Standards:
IEC 60660 – IEC 60273 -IEC60137
Installation:
Bus bar and MV equipment installation with three screws at the top of insulator.
insulator is installed with three screws on the plate.
Technical data:
Rated operating voltage24KV
Dry power frequency withstand Voltage 50 KV/1 min
Lighting impulse withstand voltage 125KV
PD 10pc>
Creepage distance 337mm
Insulator dimensions 170mm
Routine tests:
Test Rated operating voltage
Test Dry power frequency withstand Voltage
Test PD